GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

High pressure on my Optima Ferolli 901 central heating?

Hi,
I have a Ferroli optima 901 . I had problms with the DHW and foolishly adjusted this on the mod gas valve as it was varying from hot to cold all the time(after i did this i saw that it is factory set and not to be adjusted in the manual).
I now have constant hot water but evertime my central heating kicks in it rises to over 3 bar and opens the PRV .It then drops below 1 bar and stops the boiler working. I have checked the radiatiors for air and this is all ok. Should i try and vent the heat exchanger. Please someone help.
Monkey Hanger, May 2008
my pressure is at 3 bar carnt get hot water

andy, January 2009
Thanks for the fast answer. I have tried the red expansion valve, I pushed the needle and it let air out. The boiler seems to run ok if i do not put the central heating on. It stays at a constant pressure 1.5 bar uaually. As soon as the central heating comes on (when i turn the room stat from 0 to 18 degrees) the radiators will go to the correct temperature for about 1 to 2 hours and then the PSV kicks in as it has gone over 3 bar. Any suggestions anyone. Thanks for the reply ryan.

monkey hanger, May 2008
chek the expansion vessel. a big red thing usually round. it will hav a shrader valve, like a tyre valve. push the needle in and see if water comes out. if it does then its nakerd and needs to be changed

ryan, May 2008
link Click here to see other fixes for Ferroli.