Melodie asked ... How do I remove and change the basket? Duratech Identity Gu?    |    Kathy asked ... Samsung ER-4915?    |    Mark asked ... Oven door removal?    |    Jt asked ... Where to buy mt270x petrol cap?    |    Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Click here to ask your question

Vokera combi?

Both heating and hot water working fine but when heating is turned off there is a significant pressure drop... i think expansion vessel needs a charge but dont know what pressur to charge to...
Mike, June 2008
chagre as per manufacturers instructions (usually 0.5 - 1.bar)
and can only be measures with the boiler drained down, if not you are measuring system pressure no expansion vessel pressure

T, June 2008