Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Suzie asked ... Stuck Feed dog?    |    Click here to ask your question

Vokera Compact 25HE - NO HOT WATER?

we have a vokera compact 25HE, were pretty sure the pilot light isnt firing, we top'd up the pressure and still no hot water, it sounds like somethings happening but 5 mins later, still no hot water...

any suggestions?
Dan, June 2008
all combi boilers work on five points tap operated the boiler senses that hot ask for through flow switch moves motorized valve pump kicks in then the fan operates the air pressure switch operates then the condensate switch kicks in the igintion then gas output goes through the plate heat exchaNGER HOT WATER
FLASHING GREEN AWAITING THE INSTRUCTION TO THE BOILER FROM PCB TO START

SOLID GREEN LIGHT THE IS ON WORKING

RAPID FLashing green IS IGINTION ON

red check the ntc central heating thermister and condensate pipework is not choked apply heat by the means of hair dryer

tel 07831721987, December 2010
similiar problem, but the boiler is firing but very soon goes out with a flashing green light every 0.5 secs? any help or info would be appreciated

Gareth (sparky), November 2008
by toping up the presure you are only adding water (not gas) to your central heating system. be carfull not to put any more than 3 bar presure in, 1.5 bar is enough for two story house

penguin heating plumbing ltd, October 2008
look at your thermisters (litle prob with 2 wires) or your heat exchanger

penguin heating plumbing ltd, October 2008
The compact he frstly has 3 safety interlocks to satisfy 1.the water pressure switch must be made 2.the condensate pressure switch should not be made and lastly the air pressure switch then and only then does the ignition control board take over. It could just be a simple problem like venturi to the air pressure switch blocked or it could be the ignition board. If you are in sussex area call Sussex Gas on 01273 583052 they are the local Vokera agents and will not rip you off

mark, June 2008
get someone in to look at it , it might need the venturi cleaning if the fan is running but not bringing on the gas.

Big A, June 2008