3 hours ago Ela asked ... Worcester 30 Cadillac combi boiler won’t fire up and the EA?    |    Alan asked ... Problem with JCB 3CX transmission?    |    Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    Click here to ask your question

My pressure is below 1 bar and my pilot light is out and won't re-light?

I have a Ferroli Optima 701 and my pressure is below 1 bar. How do I re-pressurise? Also my pilot light is out and won't re-light following the instruction on the control panel cover?
Andrew, June 2008
to re-pressurise, locate the filling loop (usually a flexible braided hose with small handle connecting the water mains to the system water, mostly located under the boiler) slowly open lever and watch pressure rise to 1 - 1.5 bar when system is cold (if you go over, bleed excess from radiator until back to 1 - 1.5 bar)

if the system pressure is too low the boiler wont fire, maybe causing your second issue, fill first and try.

T, June 2008