Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

Sabre 29 HE running cold!!!?

Looked for answers here but unable to find any. Had the above boiler for the last 2 years and its been fine. Had my gas meter moved and since then the boiler runs cold after a few minutes. yested this on all taps and its the same. when it 1st happened the red light came on, now, the fan kicks in the burner lights the water gets hot for about 1 minute then the burner goes off and water runs cold. after about 3/4 mins the burner relights the water goes warm then the same process happens. i tested the CH also and its the same thing. Atfer the men moved my meter i asked my wife if it all went ok as i was at work and she said they had a problem to get it started at 1st and said it npossibly had an airlock, which cleared after a few mins. Could this be the fault and if so how do i clear the airlock.
Thanks for your time.

Jonny
Jonny, June 2008
Sorted it out now. It just needed a good service. There is a sensor by the flue that was killing the gas, it was cleaned out and is now fine. The flow out was hot and the return was cold.

Jonny

jonny, July 2008
sounds like one of the boilers thermisters are faulty, causing the boiler to 'think' it has reached temperature......what are the flow/return temps when boiler cycles on/off?

very doubtful it has anything to do with your gas meter

T, June 2008