Melodie asked ... How do I remove and change the basket? Duratech Identity Gu?    |    Kathy asked ... Samsung ER-4915?    |    Mark asked ... Oven door removal?    |    Jt asked ... Where to buy mt270x petrol cap?    |    Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Click here to ask your question

no water pressure on vaillant hot water unit?

have had to remove central heating units to lay new floor .When put back there was no water pressure shown on the Vailant hot water unit and an f 13 fault showed up.I have water from both the hot and cold taps but no hot water from the hot tap.What do I have to do to regain a pressure reading on my Vaillant system.There is gas in the system as I can hear the gas burner however it shuts down within minutes as there is no water pressure.
What do I have to do to rectify this problem.
Fred Grimminck, June 2008
you need to top up the system via the filling loop situated underneath the boiler, there should be a slotted lever key fitted into a 1/4 turn valve there are 2 of these valves, you need to open both Not too easy to describe but have a look in instruction manual. it needs only to be topped up to around 1 bar

Ian t, June 2008