boiler trips rcd after 30 seconds ariston euro combi?

have changed both boards.trips rcd only A23mff1
derek tisdale, July 2008
pump, fan or gas valve solenoid fault would draw enough to trip you rcb.

does pump run? if yes...pump is ok
does fan run? if yes, fan ok
then only left is gas valve soleniod

if you need to replace either fan or gas valve you must be corgi