Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

Pressure setting on Worcester 350?

Pressure Low light indicates that pressure in system is incorrect, which I think has caused system to stop working. By opening water stop tap under boiler pressure clock rises but without instructions I am unsure what pressure setting should be.
CAN ANYONE ADVISE?
Graham Todd, July 2008
Also check the pressure in the pressure vessel using a car tyre pump with a pressure gauge. The pressure in the vessel should be about 0.5 bar. If water comes out of the valve then the diaphragm has gone and the pressure vessel needs replacing (costs about £70)

Rich, September 2008
If the pressure on the gauge is 1 to 2 bar then the problem may be due to a faulty low pressure switch (costs about £20)

Rich, September 2008
when you repressurize any combi boiler it should be to between 1 and 1.5 bar.

its normal to have to repressurize every half year or so but if its having to be done very regular then you may have a leak somewhere.

chris gas, July 2008