THE FILLING LOOP ON THIS MODEL IS UNDER THE BOILER AND REQUIRES A QUARTER TURN USING A SCREWDRIVER. CHECK THAT YOU HAVE THE PRESSURE GAUGE SET TO 1BAR THEN BE CERTAIN YOU HAVE TURNED OFF THE FILLING DEVICE.
THE PRESSURE GAUGE SHOULD STAY AT 1 WHEN THE BOILER IS COLD. IF THE PRESSURE DROPS THEN YOU HAVE A LEAK OR AIR IS ESCAPING THROUGH THE BOILER AIR VENT.
(IF YOUR PRESSURE RELEASE VALVE HAS BEEN LETTING BY THEN YOU MAY NEED TO REPLACE THIS)
IF THE PRESSURE GAUGE RISES OVER TIME WHEN THE BOILER IS NOT OPERATING THEN EITHER THE FILLING LOOP IS LETTING WATER THROUGH EVEN WHEN YOU THINK ITS SHUT OFF, OR THE HOT WATER PLATE TO PLATE HEAT EXCHANGER IS SPLIT INTERNALLY AND THE COLD MAINS PRESSURE IS FORCING ITS WAY THROUGH THE SPLIT AND INTO THE HEATING SYSTEM.
IF THE PRESSURE RISES ONLY WHEN THE BOILER IS RUNNING THEN THE EXPANSION VESSEL WILL BE AT FAULT. THESE CAN BE RECHARGED WITH AIR USING A FOOT PUMP BUT IF WATER COMES OUT OF THE AIR VALVE ON THE EXP. VESSEL THEN YOU NEED A NEW ONE. WE CAN SUPPLY SPARES.
CHRIS @ GAS SPARES LTD, 230 EASTERN ROAD, BRIGHTON
01273 673800
CHRIS GAS, July 2008