Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Jacky asked ... Miele Vacuum cleaner?    |    Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Click here to ask your question

SD623 Pressure rising on heating?

Boiler fire,s up fine for hot water and heating . But when heating is left on the presure rise to 3 bar, when i turn it off it goes back to normal . Checked expansion unit presure and water came out of valve , is this the promblem .

Thanks for any help or advise i get
Paul cold at night brrrrrrr, July 2008
more than likely expansion vessel is dead if you got water from valve. vessel half is air section and half water section seperated by rubber diaphragm.

fitting remote vessel to central heating return pipe cheaper alternative than replacing original providing you have somewhere to locate as they aint the neatest of fella's

iain, July 2008