Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

How can i fix my central heating system?

can anyone help I have a fully pumped ch system which has started to play up i.e. after running for several minutes the vent pipe starts banging and crashing and i have to shut the system down. I have bleed everything several times and it doesnt seem to make a difference also it doesnt matter whether i run the pump on one, two or three. There is an air seperator above the cylinder could it be blocked? Any ideas appreciated. Thanks
Shaun, August 2008
Many thanks. Pump running fine. Emptied system and lots of sludge in f&e tank, refilled, started system. After half an hour slight banging and crashing from vent or/and feedpipe. Is this normal? Expansion tank full of warm murky water. What do I do now?
Cold water feedpipe from expansion tank to feed above air seperator is red hot. Can anyone please help? Thanks.

Shaun, August 2008
are you sure the circ. pump is working. I do not mean motor going round but working. isolate pump and take out the 4 alan screws see if pump head is attached to motor.

If this is ok then you have an air lock somewhere in the system

derekfromblackburn, August 2008