Melodie asked ... How do I remove and change the basket? Duratech Identity Gu?    |    Kathy asked ... Samsung ER-4915?    |    Mark asked ... Oven door removal?    |    Jt asked ... Where to buy mt270x petrol cap?    |    Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Click here to ask your question

WHAT TO DO?

got a linea 24 boiler and the pressure keep going up to 3 i then drain water off at a radiator down to 1.5 and after about 12 hours it goes back up.the heating is off so what do you suggest
Michael.Eaton, August 2008
Check filling loop isnt open,if thats ok either exp vessel pipe is choked or faulty expansion vessel.

Chucky, September 2008
If it is not the filling loop passing it is a faulty hot water heat exchanger. Thi is fairly easy to remove and is detailed in the manual.

Ian, September 2008
Sounds like the boiler is filling itself via a dodgy fill loop. Is there a braided hose of sorts attached to the mains cold water and heating pipe? This might be passing, filling the heating system up.

steve, August 2008