Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Katie Bond asked ... Fixing auto threader on Baby Lock Enlighten Overlocker?    |    Chris. asked ... Miele W800 novotronic washing machine?    |    Click here to ask your question

ideal claasic ff250?

the fan keeps running but no piolet light so it wont fire up............ please help.
simon, August 2008
it doesn't have a thermocouple or perm pilot,

if the fan is running and no spark its prob gonna be aps or blocked venturi etc something around there but could also be pcb prob.

a engineer will sort it

iain, August 2008
thermocouple problem

trevor, August 2008
There could be one or more of many problems.
If your boiler has a perminant piolt (ie is lit even when boiler is not running) and this has gone out then your boiler will not come on and problem could be caused by a faulty thermocoupler.
If it has an electronic piolt (ie only lit when call for demand) you could be looking at:-
Fan running but too slow to operate air pressure switch (faulty fan)
Faulty air pressure switch itself.
Faulty PCB, not sequncing the lighting procedure
Faulty gas valve (PCB sequncing but valve not operating)
You need to call a Corgi Engineer as these are not jobs to be tackled by anyone unqualified.
You can find Corgi engineers by using the postcode search @ www.trustcorgi.com

Robin S, August 2008