andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

how to fix domestic hot water?

help!...i have a baxi back boiler witch does both domestic hot water and central heating...the central heating is ok. but i have no hot water, the tank is cold..the baxi is heating the water, but not warming the tank..one pipe from the baxi going upwards is hot..but the taps are cold
stephen, September 2008
Check the small feed tank in the loft,or at the highest point,it may have run dry.Check the ballcock has not stuck in the up position,if it has give it a gentle shake it should drop and water should start running into the tank.
Also check the flow and return to the hot water cylinder,there may be some kind of air release valve valve on the fllow for airlocks.
If neither of these are the fault it`ll be the zone valve.

Gasman, September 2008
we need more info than that.
is it a fully pumped system ?
how many motorised valves have you ?
is the tank stat calling for heat ?
etc

hi-spec plumbing & heating (essex), September 2008