andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

Water returing back into C.H. system tank via the vent pipe?

fitted a new replacement pump but if I set on 2 or 3 the hot water enters the holding tank via the vent pipe
which means the water from the boiler does not pass through the pump at all. why? However set on one this does not happen & the rads get hot ok when
running on the one setting This does not seem right to me! can you advise? Please!!!!
Spike, September 2008
is the new pump the same output and head as old 1 ?, new pumps have better output , was the old pump on same speed setting ?, it will take longer 2 heat up on speed 1 , and you might get more air and corrosion in system . could b the layout of pipework doesnt suit strength of new pump

marti, September 2008