GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

baxi 105e too much pressure?

my boiler baxi 105e sits at 1.5 bar no problem but when asked for ch pressure goes up and it blows off at 2.5bar whats causing this
pawbroon, September 2008
most common problem, expansion vessel flat or dead. 95% chance its dead.

options are to recharge it if its ok but flat or
1: replace like for like vessel in boiler
2: fit remote vessel to ch system somewhere hidden.

iain, September 2008