Alan asked ... Problem with JCB 3CX transmission?    |    Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Click here to ask your question

baxi 105e too much pressure?

my boiler baxi 105e sits at 1.5 bar no problem but when asked for ch pressure goes up and it blows off at 2.5bar whats causing this
pawbroon, September 2008
most common problem, expansion vessel flat or dead. 95% chance its dead.

options are to recharge it if its ok but flat or
1: replace like for like vessel in boiler
2: fit remote vessel to ch system somewhere hidden.

iain, September 2008