Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

baxi 105e too much pressure?

my boiler baxi 105e sits at 1.5 bar no problem but when asked for ch pressure goes up and it blows off at 2.5bar whats causing this
pawbroon, September 2008
most common problem, expansion vessel flat or dead. 95% chance its dead.

options are to recharge it if its ok but flat or
1: replace like for like vessel in boiler
2: fit remote vessel to ch system somewhere hidden.

iain, September 2008