Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

Protherm 80e Combi Boiler?

Can anyone tell me how I reduce the boiler pressure please. It goes up to just under 3 Bar when I have the central heating on. i have been told that the pressure valve can/will blow at 3 Bar, which is what I am trying to remedy before it does.

i could do with some advice please.


Ta
Rod, September 2008
to the left of the diverter valve there is a drain tap you could relieve some pressure from there or even at a rad vent.you could also manually operate the emergency vent valve to reduce the pressure.

carl, November 2008
Rod,
It apears that your expansion vessel has failed which is positioned at the rear of the boiler you need a CORGI Reg heating engineer to repair the boiler safely.

Paul, October 2008