I went to a WB 28cdi yesterday, same fault, dhw light flashing rapidly. This is a fault code for air flow sensor. If you are not corgi/gas safe then DON'T touch it....call the pro's in! It is a legal requirement for anything to do with combustion components! Anyway, I managed to kick this boiler into action, if only for a brief moment. The fan sounded like it was gonna fly out of the casing, and squeaking! Bearings! Bingo! The fan was weak thus not giving the flow sensor the correct air pressure. So, this boiler needs a new fan, my thoughts are, if the fan is tired, for the price of it, I may as well replace the pressure switch at the same time. To gain access to the fan, you will have to break the seal on the cover, this seal needs to be replaced!! Anyway, once all the parts have been replaced, checks need to be made! Ie, with gas flue analysers etc... So this is not for the DIY enthusiast! Although you think you may be saving a couple of quid, but a couple of quid ain't worth saving if this is not done correctly and putting lives at risk!!! By not having it done by a qualified engineer. Boiler runs like a dream.
Simon, December 2012