GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

worcester 26cdi preasure gauge abvoe 3bar over flow dripping?

dropped presure via relife valve but it still gose back up
even if c/h is off,preasure gose up quicker if c/h is on.
help please.
shaun, October 2008
it sounds as though the plate heat exchanger is cross leaking and putting mains water pressure into the heating side.
If pressure is rising when boiler isn't running and filling loop key is removed then this is more than likely the problem, hope it helps.

joe, October 2008
thanks-filling loop valve(gery knob)offand key removed.
shall i try c/h on mains water off and see what happens to preasure then?

shaun, October 2008
Your filling loop must be still letting water through disconnect or you may have valve to turn off

stephen armstrong, October 2008