Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Suzie asked ... Stuck Feed dog?    |    Click here to ask your question

how do you lower the pressure to 1-1.5.of the vokera mynute 10 mine is 3 a?

how do you lower the pressure of the vokera mynute 10?my boiler is operating at 3 at the moment and am scared other things may blow up.

and what causes the radiator to swell up with water and finally the water bursts through the coating?how do you repair that
sarah, October 2008
Mr.Knowitall,thanx a lot for the solutions.much appreciated!I had no clue whatsoever!

sarah, October 2008
sarah have no fear that the 3bar of pressure will cause your boiler to blow up.the safety valve on the boiler will open and the excess pressure will bleed out .if you wish however to reduce the pressure to 1.5 bar the you only need to open a bleed screw on any radiator and the pressure will fall.as for your radiator it sounds very much like it has a pin hole right thru you will need to replace it.

mr knowitall, October 2008
link Click here to see other fixes for Vokera.