Sharma asked ... Replacing pin for belt guard Ranch King Pro 14AT818H205?    |    Freya asked ... Frister & Rossman Cub7 Sewing Machine?    |    katlego asked ... Rev count on my 1982?    |    andrew asked ... "SECURE" on a yellow backround, and I cant ge?    |    Melodie asked ... How do I remove and change the basket? Duratech Identity Gu?    |    Click here to ask your question

Why do I need to fill my system daily?

My boiler needs re-pressurising daily. I have checked the expansion tank @ 1 bar. I cannot find any leaks. I have installed liquid leak sealers into the system and I still have to fill the system every day.

It's a vokera linea 24 about 7/8 years old.
Bobby, October 2008
if its that old the diaphragm in the expansion vessel is probably ruptured, any water coming out of the schrader ( air ) valve.? if so it's knacked.( answer above is also correct)

richard ( heating eng'n'r ), January 2009
Unless you depressurised the radiators/boiler the expansion vessel pressure will be the same as the system pressure. The expansion vessel should be measured with zero system pressure reading on the boiler front panel. The water must be going somewhere. Either you have a leak or it is going out past the system overpressure valve. Does the system pressure go up to 3 bar when the central heating is hot? (this will cause loss of water through safety valve). If so recharge expansion vessel.

c, October 2008