george crawford asked ... Citroen C3 Picasso?    |    Maggie asked ... How can i mend my kettle?    |    Anthony asked ... Can a crack be repaired?    |    adrew asked ... Radio no sound?    |    Wayne asked ... Kd14ss program button?    |    Click here to ask your question

fellow engineers, advice on ecomax?

righty ho, vaillant ecomax firing whistling and extinguishing.

it blew a hole in the flexible re-enforced tubing on pipework to heat exchanger so boiler was off when i arrived. Replaced tubing re-filled vented everywhere possible but heat exchanger still sounds in distress. rising from about 20 deg to 80 deg in around 6 secs then turning off and waiting to re-fire on normal anti cycle time limit.

luke warm water if you're lucky and very little ch,

has anyone had similar problems with this boiler or heard any stories, im thinking blocked h/ex but they around £300 + so would have to be sure...

any help (in exchange for a handful of haribo and 50p) would be greatly appreciated.

cheers
iain, October 2008
iain

Surprised that it would fire up if the exchanger was blocked
I have never tried have you used Second diagnostic level
Failing that call makers for advise
Cheers a

a, October 2008
link Click here to see other fixes for Vaillant.