Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    Click here to ask your question

hoe can I get the pressure up! Glow worm 24cxi boiler?

Pressure had dropped.Reason unknown (not used much during the summer) and pressure dropped below 0.7 bar (should be 1.0 bar). Red light came on and boiler cut out. However, turning the filling loop knob has no effect at all. According to the instructions it's as straightforward as turning it gently until pressure rises appropriately - does this mean the valve is broken?
Mekus, November 2008
Leave the internal filling loop alone and fit an external one. This is what Glowworm recommend.

fred, November 2008
more than likely, they can shear the pin and turning does sod all. if so, replacement filling section needed.

iain, November 2008