Katie Bond asked ... Fixing auto threader on Baby Lock Enlighten Overlocker?    |    Chris. asked ... Miele W800 novotronic washing machine?    |    Larry asked ... How to stop my steam iron from leaking. Model dw2463 Rowenta?    |    HT asked ... Radio code Philips 22RC200/35?    |    Roberta asked ... DW5080?    |    Click here to ask your question

how can i drain radiators in a sealed system?

I have a sealed system (glow.worm micron100ff) and some of the radiators / heaters are not getting hot, i have been told not to drain radiators in a sealed system
pat shine, November 2008
I am sure you dont mean drain the system - you mean bleed the air out? - If you know how to refil the system then you probably wouldn't have asked this question (stupid me)

To Refill - look for a filling loop on the pipework somewhere under the boiler (not sure if this is built in on a micron) should be a braided metal flexi pipe with a valve at either end.
Turn the valve to let in water while keeping an eye on the pressure gague on the boiler - making sure that you dont let it go over 1.5. shut off valve when 1.5 - then bleed air from radiators. - repeat until all rads are done then make sure gague is between 1 and 1.5 fill as needed, rads should get hot.
If you are really stuck with this or have no idea of what i just wrote - then reply to this with an email address and i can put some diagrams in that.

OR depending where you are in the country and how big the property is - a nice plumber should do this for about £35.

Stewiesnake, November 2008