Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

Vaillant Turbomax GB 242 - no pressure?

We have just bled our radiators and expelled lots of air, but not there is O pressure on the boiler and no heating or hot water.
Jane, November 2008
if i remember the filling loop is built in on this model so ....here we go !.... look up underneath boiler and ther are 2 small brass blocks about the size of oxo cube they will be to the rh side of boiler as your looking at it, in the middle of these "oxo's" you will see a slotted screw, open one (so its inline with pipewrok) and then the other at this point you will hear it filling and see pressure going up.....set to 1.5 bar and vent rads then re set to 1.5.....job done !
oxo's

mark the gay boiler man, November 2008
find the filling loop. its a fexible hose with a tap at each end. open one tap then open the other untill the pressure gos up to 1 bar

b, November 2008