Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

my worcester 30 cdi combi boiler wont fire up and ''ea'' keeps flashing?

my worcester 30 cdi combi boiler wont ignite and 'EA' keeps flashing along with the big blue button. The water is above the 1 which i think is fine so why not working????
annon, December 2008
Fab advice
Poured kettle on white outlet pipe and a large lump of ice followed by water came out.
Restarted boiler and all fine...yay!!

suzi, January 2016
DIFFERENT REASON TO THE ABOVE:
My EA problem was nothing to do with the condenser drain, instead the heat inside the boiler had caused the spark plugs to get too close together and it wasn't sparking efficiently enough to ignite the gas. This was diagnosed and fixed by the guy who installed it, I wouldn't advise a home-made fix unless you know what you're doing.

Tom, January 2011
I had the same problem this morning(Christmas day!!!) had previously resolved it with a kettle of water so followed the same routine. However, 6 kettles later and I still had EA flashing on the unit. I removed the white flexi pipe from the underside of the boiler and drained about 2 pints of water from it, reset the boiler and hey presto, all working again.

Adrian, December 2010
Panic over! Thank you for the excellent advice!

Dutch Boy, December 2010
hi we had the same problem.put hot water after reading all of ur posts.
Its working now.
Thank you so much every single one of you.
Have a great X'mas.

jay, December 2010
same problem here EAflashing on control panel no heating or hot water 22m outlet frozen at ground level hot kettle poured over pipe happy days boiler works fine stress levels back too normal hope this helps

ian s.wales, November 2010
brillant, it did take me a few attempts with the kettle, i didnt want to make it too hot but after 3 goes, i tipped 1 full boiling hot kettle over it, and wacko its working. had this boiler for some time, and every so often it did this, and used to just leave it, but now know the fix , a brillant thread, thanks guys

drJones, October 2010
Hi
Thank you all. This forum has probably saved me £100-plus on a plumber call-out. My Worcester Greenstar condensing boiler stopped working too and I got the "EA" letters flashing. Resetting didn't work.

I thawed the outlet pipe outside the house that led to the drain, which was blocked with thick ice. A couple of kettles of boiling water sorted this.

The boiler still didn't fire up at this point so I disconnected the white condensing pipe that leads from the bottom of the boiler and drained the condensed water into a bucket. I reconnected it to the trap/discharge pipe and the boiler fired up first time. It's been fine since...

Jason H, January 2010
You people are all saints. Had a whole day with no heating and getting EA fault, just read this board and you have solved my issue. Because it is dark outside I was able to use a bucket and just pull the flexible white hose off inside the boiler, and about 2 pints of water came out. Boiler started no problem. Thank you and god bless you all.

Burl Ives, January 2010
woo hoo my worcester greenstar 42cdi combi boiler problem was flashing ea at me and thanks to this forum I found the condensate drain frozen - kettled it & a-ok so far
thanks be to the internet!!!

drinkstable, January 2010
Hi thanks for the advice, just drained the condensation outlet pipe (under the boiler) and hey presto the EA error sign has gone and it has started up again! all this because the waste pipe outside was frozen, thanks again.

Magpie33, January 2010
Just had exact same problem and also managed to fix it by pouring hot water on the pipe outside.

funny how many people posting this month, this cold snap is really taking its toll.

Paul, January 2010
I had the same problem. I tried pouring hot water on the pipework but no joy, so found the point at which the boiler connected to the piping (just underneath the boiler). There was a flexible water cable. Took that out of its fixing with the plastic piping and fed it into a bucket. Water started to come out and the boiler is now working.

Mark Dempsey, January 2010
I had the same problem. I tried pouring hot water on the pipework but no joy, so found the point at which the boiler connected to the piping (just underneath the boiler). There was a flexible water cable. Took that out of its fixing with the plastic piping and fed it into a bucket. Water started to come out and the boiler is now working.

Mark Dempsey, January 2010
Just forgot to mention I defrosted the pipe by boiling a kettle couple times and pouring on the frozen pipe outside no more EA error codes boiler working fine again

Sam, January 2010
I just had the same issue and it also turned to be frozen condensation pipe outside its the 15mm pipe that runs from the boiler.

Sam, January 2010
Hi I just had the same fault an after a little investigating it turned out to be the condensor trap outlet was blocked. This was running to the outside drain and had become frozen! this blockage stop the boiler from firering and caused the EA fault code. This is only one cause for the EA code there are others. I imagine you have fixed your boiler by now but for any others with this issue in the future reading this I hope it helps.

mrMADavis, January 2009