Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    wendy asked ... Old Creda Solar Plus Cooker will not come on?    |    Click here to ask your question

worcestre 28cdi - increasing water pressure?

Why is boiler pressure still increasing to blow off when filling key out of boiler and water valve shut off?

Any ideas?
Billy B, December 2008
It sounds like the domestic heat exchanger has an internal leak, meaning that the mains pressure cold water, being a higher pressure than the boiler system pressure (1.5 bar), is flowing in to the system, raising the pressure. You can check this by turning off the cold water service valve underneath the boiler, and blasting off the pressure to 1.5.
The pressure should stay level over a period of time. Have the boiler switched off for this so that it doesn't rise with the heating coming on.

scott, December 2008