Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Jacky asked ... Miele Vacuum cleaner?    |    Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Click here to ask your question

pressure too high ?

my ariston boiler goes too 3 bar from 1 bar idle
rj, December 2008
either the filling loop is passing or the heat exchanger is split, also look at the expansion vessel check it is pressurised.

richofix, January 2009
expansion vessel is either depleted of air or its hole'd...drain boiler check air charge in vessel with foot pump (should be round 1 bar) if its empty then pump to 1 bar

mark the gay boiler man, December 2008