ignore id**t above. system pressure on sealed system should be 1 bar when cold. anything near 3 and safety valve could discharge as well as leak out of any suspect pipework. system pressure gauge could be blocked. should be a silver filling loop that connects from cold water inlet on boiler to heating return pipe under boiler, open valve or valves slowly until pressure at 1-1.5 bar then reset boiler. if no good call engineer.
spook, January 2009