1 hour ago Bob asked ... Charger fault?    |    Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    Click here to ask your question

water pressure?

The water pressure drops after each time the boiler has been on therefore it doesn't start at the time programmed until the tap is turned to make the white needle go up to the red bar needle.
Norman, December 2008
Open the pressure release valve and allow water out until boiler dial reads zero. Connect a footpump to the pressure vessel tyrevalve tytpe connector and pump it up to 1 bar reading on the footpump dial, (boiler dial should still read zero, if not keep the boiler pressure release valve open). Once footpump dial stays at 1 bar and boiler stays at zero you are almost done. Disconnect footpump, turn off release valve and repressurise to just over 1 bar using the tap either side of a flexible hose, or however you normally do it.

robbie repairs, December 2008