the answer to most of the problems listed is that there is water instead of air in the primary expansion vessel.when the water in the boiler heats it expands into the air in vessel, compressing the air, if the vessel is filled with water, as water does not compress,it comes out of pipe sticking out of house via pressure release valve. to remedy this take off top cover and the two topmost front covers(1 of grey). bleed off all the water from system via PRV(turn red knob towards you about an eighth of a turn until you hear water flowing out) do this until pressure drops and low pressure warning comes up on display or until you stop hearing water flowing. next, on the primary expansion vessel, which is located at the top left of the boiler(grey in colour),you may have to take off metal cover to access, there is a valve at the front(same as you get on a car tyre), take off cover and use a bicycle pump to pressurise to 2 bar, your digital display will let you know when you have reached this, take off pump and press pin in valve to bleed off pressure down to about 1.3 bar. thats the job done apart from replacing all the covers that you took off. very easy DIY job that you can do in 20-30 minutes with a phillips screwdriver and bicycle pump. good luck
billy gibson, January 2010