Ela asked ... Worcester 30 Cadillac combi boiler won’t fire up and the EA?    |    Alan asked ... Problem with JCB 3CX transmission?    |    Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    Click here to ask your question

What is causing leak from overflow pipe on baxi combi instant 105e?

Leak from overflow pipe on baxi combi instant 105e of about 2 mugs a night. Consequently boiler not firing up.
Sue Walters, January 2009
it is the 3 bar blow off valve take the front off and you will see a red knob with 3.2bar on it turn it right a little it should click out and and the overflow will stop happened to mine :-) hope it helps

James Gale, February 2009
pipe to expansion vessel blocked had this problem alot

billy, January 2009
Check system pressure not rising when boiler is fired. I've seen this when expansion vessel pressure low or failed.

Big T, January 2009
PRV needs replacing

b, January 2009
link Click here to see other fixes for Baxi 105E.