Bob asked ... Charger fault?    |    Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    Click here to ask your question

What is causing leak from overflow pipe on baxi combi instant 105e?

Leak from overflow pipe on baxi combi instant 105e of about 2 mugs a night. Consequently boiler not firing up.
Sue Walters, January 2009
it is the 3 bar blow off valve take the front off and you will see a red knob with 3.2bar on it turn it right a little it should click out and and the overflow will stop happened to mine :-) hope it helps

James Gale, February 2009
pipe to expansion vessel blocked had this problem alot

billy, January 2009
Check system pressure not rising when boiler is fired. I've seen this when expansion vessel pressure low or failed.

Big T, January 2009
PRV needs replacing

b, January 2009