Bob asked ... Charger fault?    |    Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    Click here to ask your question

Baxi combi is loosing pressure?

My Baxi combi 105e keeps loosing pressure! It seems to be ever since I removed the bathroom radiator whilst tiling and is becoming more frequent. I replaced the boiler treatment, blead the air and repressurised the system. Was I supposed to do anything else or is this a coincidence?
Mike Richards, January 2009
when the boiler is runing how high is the pressure geting on the boiler,if you have no leaks it could be the pressure relif valve letting by(check the prv pipe outside to see if its been driping)or the expansion vessel might need recharging the 105 uses the expansion vessel for the preheat on hot water, has the hot water been ok,the pressure guage should be 1 bar cold and 2.5 max hot

jim, January 2009
no signs of any leaks ?

Jazz drummer, January 2009