Ela asked ... Worcester 30 Cadillac combi boiler won’t fire up and the EA?    |    Alan asked ... Problem with JCB 3CX transmission?    |    Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    Click here to ask your question

Baxi combi is loosing pressure?

My Baxi combi 105e keeps loosing pressure! It seems to be ever since I removed the bathroom radiator whilst tiling and is becoming more frequent. I replaced the boiler treatment, blead the air and repressurised the system. Was I supposed to do anything else or is this a coincidence?
Mike Richards, January 2009
when the boiler is runing how high is the pressure geting on the boiler,if you have no leaks it could be the pressure relif valve letting by(check the prv pipe outside to see if its been driping)or the expansion vessel might need recharging the 105 uses the expansion vessel for the preheat on hot water, has the hot water been ok,the pressure guage should be 1 bar cold and 2.5 max hot

jim, January 2009
no signs of any leaks ?

Jazz drummer, January 2009