Bob asked ... Charger fault?    |    Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Matt Longmore asked ... Non-start on Flymo XLT 250?    |    John asked ... How to fix my fireplace?    |    Ian Scott asked ... Remove cover off gas boiler?    |    Click here to ask your question

How can i fix my valliant combi?

My valliant combi boiler keeps pouring hot water out of its outside overflow pipe, yet the heating and hw still work ok. Also I have to keep filling the system up using the valve at the base.....any ideas please
Dp, February 2009
You may have left the filling loop open when you have filled it up in the past. When you pressurise the system always fill the system when cold other wise you can damage the heat exchanger.(PRESSURISE TO 1 BAR)
Also if the pressure gauge rises over 3 bar after you have correctly filled the system and water is expelled from the pressure relief there could be a problem with the expansion vessel.The expansion vessel may have a damaged diaphragm or may have just lost charge which should be around .75 to 1 bar.This should be checked by a corgi engineer.

Russ Davies, February 2009