Morne asked ... My defy dtl 125 toploader?    |    Ernie asked ... How to fix gearchange ldv maxus van 2006?    |    Cuckoo asked ... Changing batteries on a fixed bt corded phone?    |    Marc Nollid asked ... Nissan Micra mk 5 2018 rear seat mecanism?    |    Maggie asked ... New Home 535?    |    Click here to ask your question

0pressure obvious things checked! help!!!?

i have a modena 80e ferroli boiler that is ok when the heating is on and then when it is off loses all its pressure the automatic air vent was leaking so it was changed and its still happening . i have had e new expansion vessel and pr valve to no joy .

there is no obvious leaks - any ideas?
kirstynurse, February 2009
check pressure vessel is sound with right air pressure
see if gauge is going up when heating is on may be discharge to P valve and gauge down when system cold. than p. vessel not correctly size i gess

Mr K, February 2009