Mike asked ... Bosch WTA74200GB Vented Dryer?    |    Stuart G asked ... C3 Front Wiper control problem?    |    Clare S asked ... Repair Electriq dehumidifier?    |    Bob asked ... Charger fault?    |    Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Click here to ask your question

Micron 60FF boiler?

Worked fine til 2 days ago. Now the CH is fine but i have no hot water. If timer for both comes on boiler fires up, however, if i just want hot water, the boiler does NOT fire up. Why & help.
Janet Golby, March 2009
sequence of operation for hot water, programer then hot water cylinder stat, zone valve /y plan valve which closes a switch in valve which sends power to fire boiler .so you need to know if you have two zone valves or one y plan valve the fault is on one of these or the programer or cylinder stat 240volts so becarefull i would get a heating engineer

craig bg, March 2009