mike asked ... Fisher & Paykel 913t dishwasher?    |    Emma asked ... Foot pedal smoking?    |    Morne asked ... My defy dtl 125 toploader?    |    Ernie asked ... How to fix gearchange ldv maxus van 2006?    |    Cuckoo asked ... Changing batteries on a fixed bt corded phone?    |    Click here to ask your question

sime friendly format 80 e pressure problem ??

hi, my sime boiler has a problem with building up pressure. the hot water side works perfectly. however if the heating side is bled down so no pressure is in the system, after about 6 hours the system will be regestering 3 bar pressure and the safety valve will start releasing water.i have checked the top up valve and this is not leaking. can anyone suggest a possible cause ???
earle, March 2009
the same was with mine,check the 1 way vault ,its the 1 that lets the water in 2 fill the radiators up when pressure is low, its a silver connection pipe that connects the copper cold water pipes together. sorry idont know the name of it but it might be called a nonereturn valvue.

Grabo, March 2009