Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Jerry asked ... Alpine 7287?    |    Guy asked ... Gaggenau fridge alarm problem?    |    Click here to ask your question

Home Heating System Vaillant 835/E2 - F25 ERROR?

Hi,

I have had the error F25 appear on my boiler and as a result have filled it with water to raise the pressure levels to between 1 and 2. However after 15-20 minutes the pressure level is back to zero and the error F25 is on screen again. I have checked that all the radiators are hot which they are and cannot see a visible leak. Please help!
Vix, April 2009
check pressure release valve pipe going from boiler through the wall to outside 15mm pipe, see if it is passing water and also check the pressure in your expanssion vessel if water cums out of the valve it nakered

STE, April 2009