Mike asked ... Bosch WTA74200GB Vented Dryer?    |    Stuart G asked ... C3 Front Wiper control problem?    |    Clare S asked ... Repair Electriq dehumidifier?    |    Bob asked ... Charger fault?    |    Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Click here to ask your question

danesmoor 12/14 lockout on the burner?

over the last 10 months my boiler has gone to lockout. sometimes the boiler might run for 2 months, no problems, then it might lockout twice in 2 days, had new coil fitted control box, photocell but still no joy any idea guys. parts fitted by a oftec engineer. he's baffled and fed up with it
john, April 2009
thanks i shall try that

john, April 2009
I have known the Ignition Transformer Dafoss EBI type to cause this type of erratic lock out, worth a try if all else has failed

Boiler Repairman - Ipswich, April 2009
co2 running at 10.8 thanks for the suggestion

john, April 2009
Could be a Flue Problem - badly sited balanced flue which causes problems in certain wind/weather conditions?

Silly Question, but has the Burner been set up using a combustion analyser? 10.5 - 11.0% CO2

Boiler Repairman - Ipswich, April 2009