Andrew - C asked ... Stannah 400?    |    Liam asked ... Belts for old WEBB Mower?    |    Leith asked ... Bosch Classix Type WKM41 front loader washing machine?    |    Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    Click here to ask your question

Pressure fluctuation on Potterton Powermax HE?

I have a 3 yr old Potterton Powermax boiler and apparently if the burner is on the pressure is going too high and goes to E01 error code, if the burner is off the ressure is going as low as 0.5? Has anybody had this problem before. Can there be any leak?
Ekta, May 2009
Check the Air Charge in The Expansion Vessel should be 1-00 Bar with the vessel drained

www.elanar.co.uk, May 2009