andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    tom dimmock asked ... How can i mend the lid on russell hobbs elec?    |    Click here to ask your question

Why do the upstairs radiators come on when i run the bath?

I have a Glow-worm 38cxi combi boiler. Just recently the hot water runs just warm even if it is turned to maximum. Also the upstairs radiators come on when i run the bath. The boiler is only 3 years old.
Ken, May 2009
This diagram...

http://www.diyfaq.org.uk/plumbing/combi.html

shows the paths for hot water and heating - if the diverter valve is in the wrong position (stuck half way) the heat output might be shared between rads & taps even though it should all go to the taps.

I would suspect the diverter valve being defective and causing your problem.

Peccavi, May 2009