3 hours ago Alan asked ... Problem with JCB 3CX transmission?    |    Lou asked ... Mac Allister 35cm electric lawn mower?    |    Ronald Charlwood asked ... Beko fridge/freezer not cold enough?    |    John Broadbent asked ... Advise?    |    suzy asked ... Brother kh-940 not in sync with DAK9 in interactive knitting?    |    Click here to ask your question

Sime boiler heating only at approx 40 degrees?

I had larger diameter gas pipes to gas meter put in for a new kitchen stove & now although dial on full temp is 40 and it takes all day to heat house. Visible flame is quite low. If I need to bleed how do I proceed or something else?
Russell, May 2009
I would guess from what you say that the new gas pipe arrangement is restricting the gas supply to your boiler.

Here's a link to some boiler engineers arguing about it...

http://www.diynot.com/forums/viewtopic.php?t=45752

Call in a heating engineer and have him measure the gas pressure at the boiler.

Peccavi, May 2009