4 hours ago Jo asked ... How to engage clutch on old sewing machine to engage needle?    |    Jacky asked ... Miele Vacuum cleaner?    |    Ben asked ... Toyota Yaris French or Japanese?    |    Andy asked ... How can I mend my MacAlistair 450w hedge trimmer?    |    Felix asked ... Hitachi vt-m70em?    |    Click here to ask your question

Sime boiler heating only at approx 40 degrees?

I had larger diameter gas pipes to gas meter put in for a new kitchen stove & now although dial on full temp is 40 and it takes all day to heat house. Visible flame is quite low. If I need to bleed how do I proceed or something else?
Russell, May 2009
I would guess from what you say that the new gas pipe arrangement is restricting the gas supply to your boiler.

Here's a link to some boiler engineers arguing about it...

http://www.diynot.com/forums/viewtopic.php?t=45752

Call in a heating engineer and have him measure the gas pressure at the boiler.

Peccavi, May 2009