Mike asked ... Bosch WTA74200GB Vented Dryer?    |    Stuart G asked ... C3 Front Wiper control problem?    |    Clare S asked ... Repair Electriq dehumidifier?    |    Bob asked ... Charger fault?    |    Terry nelson asked ... How to remove the flexible shaft from a curved shaft ryobi t?    |    Click here to ask your question

IDEAL ICOS HE24 BOILER IGNITION BANG?

Our HE24 Ideal condesating gas boiler is now 4 years old and has started to have a loud ignition bang when the programmer demands hot water. This only occurs when the pre-set timer on the programmer hits the hot water on times and does not happen if you turn up the wall thermostat to turn the central heating on. Everything works fine except for this loud ignition bang on hotwater startup. I cannot understand why the hot water demand which is set for twice a day should be any different from the central heating demand triggered by the wall thermostat, any ideas anybody?
Padder, June 2009
Burner needs Cleaning, Hot Water firing rate is higher than central heating, therefore can start with a Bang

A Gas Safe Registered Engineer should be able to Strip and clean this for you in about One hour..Make sure he checks the Combustion with an Electronic Analyser CO2 should be about 8-8%