2 hours ago Carol asked ... How to remove roller from lawnmower?    |    Ariana Orellana asked ... Code?    |    Lynnie asked ... BT Studio 4500 cordless telephone?    |    David Dawes asked ... How to recoil the starter spring - Champion R484TR?    |    peter high asked ... How can I set time on my Neff oven?    |    Click here to ask your question

WE HAVE FLUCTUATION ON THE PRESSURE GAUGE. HAVE REPLACED VALVE, BAXI 105E?

PLEASE COUL;D SOMEONE HELP? WE HAVE BEEN HAVING PROBLEMS WITH OUR COMBI BOILER, FIRSTLY THE PRESSURE VALVE LEAKED, AND THE CENRAL HEATING WOULD NOT WORK, UNLESS YOU TOPPED UP THE WATER. WE CHANGED THE PRESSURE VALVE, BUT NOW THE PRESSURE GAUGE IS CREEPING UP WHEN RADS ARE ON AND DROPPING RIGHT BACK WHEN THEY ARE OFF. THE PRESSURE WILL NOT STABILISE. PLEASE COULD YOU HELP, ITS COLDDDDDDD. THANK YOU, SARA. PS. ITS A BAXI COMBI 105E WITH STORAGE FOR INSTANT HOT WATER.
SARA BROOKS, February 2006
expansion vessel requires repressurising with air or replacing.

andy, February 2006
incase anyone else has the same problem. it needed pressurising, which the plumber did with a footpump. was not an expensive job. you could probably find out how to do it yourself. best of luck.

sara, February 2006