Eed asked ... Brother KR850?    |    Lynne asked ... Disable Alarm Scantronic 9800?    |    Ron Minadeo asked ... Table won't close all the way?    |    Cam asked ... How can I fix my Bison 50 stairlift?    |    Alfred Briffa asked ... How to build a battery conversion adapter?    |    Click here to ask your question

friendley formate 80 E water tempurture problem?

i have problem with water tempurture which is cold and then gets warm and cold again it dose not stay hot or warm . the presure is good
mike, February 2006
It sounds like you have a partially blocked plate heat-exchanger, the only way to cure it would be to remove it and flush it out or better still replace it.
Magnatite from the system blocks these so have the system flushed at the same time as you change the plate heat-exchanger and it should stop it happening again.

Kevin, a boiler engineer, February 2006