Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Suzie asked ... Stuck Feed dog?    |    Click here to ask your question

vokera linea 28 over presure?

I have a linea 28 and when i turn the heating system on the pressure rises with the temp till it hits 70 degrees and 3.2 bar however at 3 bar the safty valve ( wich is new & I just replaced ) kicks in and it looses warter from the overflow pipe till the pressure falls below 3 bar then it stopes and is OK till it is used again and then i have to re pressurise the system from 0.5bar to 1.5each time its used.
Dave L, October 2009
The expansion vessel (usually a large red tank) needs attention...maybe only repressurising with air or replacing if the internal diaphragm has split.

John, October 2009