It's a Vaillant Turbo boiler, functioning fine as regards the central heating, but no longer supplying hot water to the shower. Still getting hot water to the sink in the kitchen (next to the boiler) though. Any advice? What I know points towards the divertor valve, but wondered if anyone else can shed any light?
Kyle, March 2006


done
Hi,


It's a Vaillant Turbo boiler, functioning fine as regards to the central heating, but no longer supplying hot water? Even on maximum heat, it gets warm then cools down, then gets hot and then cools down again, its not possible to have a hot shower.

We are insured by British Gas - when they came, they said there was nothing wrong with it. Two years ago they changed the diverting valve, since then the problem started getting worse, any help? thanks

Ali, February 2010
on your mixer shower the hot water inlet has got filters it is blocked, dis connect shower and remove shower mixer and clean filter (gauze) wash and put back you will find it should cure your problem..


asghar

ASGHAR NABI, March 2006