GG asked ... Fix food processor motor?    |    T asked ... How do I turn the delay off on Electrolux DX302 dishwasher?    |    Helen asked ... How can I mend my Kenwood Gourmet FP505?    |    Roy Turner asked ... Kohlangaz Gosford HE fire?    |    Peter asked ... How can I mend a Powerwasher PRO PRO1800PWE?    |    Click here to ask your question

Water pressure drops, water expelled through overflow?

My boiler is a Glow worm Swift flow 80e Fanned flue Combination. 10 years old but not really had much use.
Each time I use the central heating, with the water level reading set at 1.5, water is ejected through the outside overflow.I know that is definitely where it is going as I set up a bottle to collect it. Once the boiler has cooled I can see that the pressure has dropped to 0.7 or so. It means I am constantly refilling to 1.5. Several plumbers have come and changed small bits, at vaste expense, in an attempt to rectify this problem but to date no luck.Any advice gratefully received so that I can at least sound as if I know what I'm talking about to the next plumber! Should I give up, do I need a new boiler? If so what would you recommend fo a one person household.Thank you.
Clare, October 2009
The 'plumber' needs to replace the pressure release valve, or PRV. Every combi boiler has one. For some reason, once these things have opened, they rarely seal themselves again, which is a complete bore. The valves cost around a tenner - fitting time? Unknown.
Plumber man should also check that your expansion vessel has around 10 psi of air in it, and the system needs to be at low pressure when it is being filled. Thats it, in a nutshell. I'm no fan of the Glow worm, and if it does need replacing, consider the Vaillant Ecotec range. Good kit.

John, October 2009