Pam asked ... Do I need to open the housing to dry the motor?    |    James asked ... Remove enterprise enrolment from an Asus Chromebook C523N?    |    tom schwartz asked ... Bosch maxx 6?    |    Noman asked ... Reverse light switch?    |    Suzie asked ... Stuck Feed dog?    |    Click here to ask your question

Vokera 24, 28 Compact?

Pressure has risen to 3 bar where it sits fairly consistently.

Water is continuously flowing out off overflow pipe on roof.

Any suggestions?
puzzled, October 2009
Common problem with this boiler . Combined heat exchange . They break down and leak. the mains water is leaking across, new heat exchange required

Mick, November 2009
filling loop tap not closed properly?. Does the problem go away if you turn of the DHW inlet tap and depressurise the dhw system by opening a hot water tap (possible leak across the dhw heat exchanger if so). If it only happens when system hot, and pressure drops very low when cold its the expansion vessel.

c, October 2009