3 hours ago Karen asked ... Royal 480nt cash register?    |    andrew smith asked ... 2009 fiesta 1388 cc titainum?    |    Eric asked ... Strimmer fuel line?    |    Frank asked ... Working fine. No cold air?    |    c.m.brown asked ... Replace chuck on aeg power drill sb2e 700r?    |    Click here to ask your question

Boiler water pressure?

I have a Ferroli SYS 10-23 central heating/hot water boiler with very low water pressure in the central heating system......as shown on the boiler hydrometer. I've tried raising the pressure using the 'pressure loop', both while the boileres working and not working, & there is no increase in pressure registering on the pressure guage. Does the pressure loop need to be open for an extended period before any increase in pressure will occur ? I've checked water flow through the loop and that seems fine. Can anyone offer any advice please ? Thank you.
Martin, November 2009
checkvalve on filling loop conected to boiler prob faulty

albob, November 2009